MODEL
|
M33KTIE
|
M40KTIE
|
INPUT (DC)
|
Max. DC input power
|
33800 W
|
|
Max. DC input voltage
|
1000 V
|
Starting voltage
|
200 V
|
Max. DC input current
|
3 × 23A
|
MPP voltage range
|
320 ~ 900 V
|
Full-load MPP voltage range
|
480 ~ 800 V
|
580 ~ 850 V
|
Number of MPP inputs
|
3
|
Nominal DC input voltage
|
620 V
|
680 V
|
DC terminals
|
2 × 6
|
MPPT efficiency (static)
|
> 99.9%
|
Withstanding voltage & insulation for DC input against the enclosure
|
Basic insulation 3000 Vdc / 1 min
|
OUTPUT (AC)
|
Rated output power
|
30 KW
|
36 KW
|
Max. apparent power
|
33 KVA
|
40 KVA
|
Rated output voltage
|
3 × 380 / 400 / 415 Vac +N+PE
|
3 × 277 / 480 Vac +PE
|
Rated output current
|
3 × 45.9 A
|
Max. allowable output current
|
3 × 48 A
|
Rated frequency
|
50 Hz / 60 Hz
|
DC component
|
< 0.5% (rated current)
|
THD
|
< 3% (rated power)
|
Power factor
|
0.8 leading ~ 0.8 lagging
|
Withstanding voltage & insulation for AC output sides against the enclosure
|
Basic insulation 3000 Vdc / 1 min
|
EFFICIENCY
|
Max. inverter efficiency
|
98.7%
|
98.9%
|
Europe efficiency
|
98.4%
|
98.5%
|
PROTECTIONS
|
Input reverse connection protection
|
Yes
|
DC input switch
|
Yes
|
DC overvoltage and overload protection
|
Yes
|
Output AC short-circuit protection
|
Yes
|
AC overload, overcurrent limitation and protection
|
Yes
|
Grid over / under-voltage and unbalanced protection
|
Yes
|
Grid over / under-frequency protection
|
Yes
|
Leakage protection
|
Yes
|
Lightning protection
|
Yes
|
Islanding protection
|
Active and passive protection
|
DC surge protection
|
Yes
|
AC surge protection
|
Yes
|
Insulation resistance testing protection
|
Yes
|
CERTIFICATES AND APPROVALS
|
Certificates
|
VDE / TUV / CE / CQC
|
Grid-connected standard
|
TUV / VDE-AR-N-4105 / G59
|
EMC / safety
|
EN 61000-6-2, EN61000-6-3, EN 61000-3-2, EN 61000-3-3, EN 61000-3-11, EN 61000-3-12, EN / IEC 62109-1, EN / IEC 62109-2
|
DISPLAY AND COMMUNICATIONS
|
Display
|
LED indicators / Bluetooth / APP
|
RS485
|
Yes
|
USB
|
Yes
|
PLC
|
Optional
|
APP and Bluetooth
|
Yes
|
OTHERS
|
Standby loss
|
< 15 W
|
Topology
|
Transformerless
|
MTBF
|
40000 h
|
Warranty
|
Standard 5 years, optional 10 / 15 / 20 / 25 years
|
Operating temperature
|
– 25 °C ~ + 60 °C
|
Cooling
|
Natural cooling
|
Relative humidity
|
0 ~ 100% non-condensing
|
IP rating
|
IP 65
|
Max. operating altitude
|
3000 m
|
Dimensions (W × D × H) (mm)
|
260 × 580 × 800
|
Packaged dimensions (W × D × H) (mm)
|
345 × 690 × 935
|
Net weight (kg)
|
≤ 65
|
Gross weight (kg)
|
< 70
|